STS Series

A static transfer switch is a two-position, semiconductor system that can automatically or manually switch between two synchronized single-phase or three-phase AC sources without interrupting the load for more than 1/4 cycle.
  • Features
  • Parameters
  • Documents
  • Get a Quote

Features

  • Smart control with DSP technology
  • Thyristor-controlled switching architecture
  • Automatic and manual transfer capability
  • Fuse-less design (seamless transfer)
  • Adjustable alarm relay outputs
  • Modbus communication (RS232 / RS485)
  • Return transfer delay and blocking adjustment
  • Automatic startup and recovery after fault
  • Smart fault diagnosis system
  • Full system measurement (Volt, Current, Frequency, etc.)
  • Visual and audible alarm system
  • AC fault, over-temperature, and short-circuit protections

Options

  • Analog measurement indicators (Volt, Ampere, Hz)
  • Thyristor fault detection system
  • Transducer support (4-20mA / 0-10V)
  • Cabinet heating
  • Fan fault monitoring
  • Remote monitoring and control

Advantages

  • Ultra-fast transfer time (<4ms / <5ms)
  • Easy maintenance and service with hot-swap modular design
  • Redundant power supply (up to 4 units)
  • Long-life design (20 years target usage)
  • Overload withstand up to 200% (optional 300%)
  • Uninterrupted power transfer for critical loads

 

3 PHASE
Model STS350 STS363 STS3100 STS3150 STS3200 STS300 STS3400 STS3600 STS3800
Current (Nominal) 50A 63A 100A 150A 200A 300A 400A 600A 800A
Voltage 200/227/380/400/415/440/460/600VAC (3F + N + PE)
Voltage Range ±15% (Transfer when out of range)
Frequency 50/60Hz
Frequency Range 45-65Hz (Transfer when out of range, adjustable)
Efficiency >99%
Transfer Type Break before make
Transfer Options Automatic / Manual / Remote
Transfer Time <4ms (synchronous) / ~10ms (non-synchronous)
Switching Structure 3-pole or 4-pole
Crest Factor 3:1
Overload 100-110% continuous / 100-125% 10 min / 125-150% 1 min / 150-200% 10 sec / >200% 250ms
Protection Overload, short circuit, over-temperature, backfeed, SCR fault, out-of-sync protection
Communication RS232 (Standard), RS485 / TCP-IP / SNMP (Optional)
ENVIRONMENT
Cooling Fan-cooled (dual redundant), natural (optional)
Operating Temperature 0°C – 50°C
Storage -10°C – 70°C
Humidity <90%
Protection Class IP20 – IP66 (optional)
Standards EN62310-1 / EN62310-2 / EN62310-3
MECHANICAL
Weight Determined by EPC
Dimensions 500×450×1000 / 600×600×1300 / 750×700×1600 / 1000×800×2100 mm
1 PHASE
Model STS1016 STS1032 STS1050 STS1063 STS1100 STS1150
Current 16A 32A 50A 63A 100A 150A
Voltage 110/127/208/220/230/240/265VAC (1F + N + PE)
Voltage Range ±20%
Frequency 50/60Hz
Frequency Range 45-65Hz
Efficiency >99%
Transfer Type Break before make
Transfer Options Automatic / Manual / Remote
Transfer Time <4ms / ~10ms
Switching 1-pole or 2-pole
Overload 100-200% load tolerance
Protection Short circuit, over-temperature, SCR fault