SD Series

SD Series rectifier and battery charging systems offer high-performance solutions designed to provide reliable and uninterrupted DC power in industrial applications. Thanks to its DSP (Digital Signal Processor)-based intelligent control infrastructure, the system operates with high stability and precision, ensuring safe energy conversion with an isolation transformer at the input. It optimizes battery life and guarantees system continuity by adapting to different battery needs with float, equalize, and boost charging modes.

With extensive language support, a user-friendly interface, and monitoring and control capabilities via RS232/RS485, the SD Series simplifies operational processes. Its active parallel operation feature allows multiple devices to work together, while battery temperature compensation and advanced battery test functions continuously optimize system performance. Adjustable parameters, programmable structure, and advanced alarm systems offer users maximum control and flexibility.
  • Features
  • Parameters
  • Documents
  • Get a Quote

Features

  • Built-in isolation transformer at the input
  • Smart control with DSP and high reliability
  • Float, equalize, and boost charging modes
  • Multi-language support (Turkish, English, German, Dutch, Portuguese, Spanish, Russian)
  • Monitoring and control via RS232 / RS485

 

Options

  • Active parallel operation (load sharing up to 4 devices)
  • Battery temperature compensation (automatic voltage adjustment based on temperature)
  • Battery test feature with adjustable voltage and duration
  • Color TFT touchscreen
KEY FEATURES
Model SD-1 SD-3
Input Phase Single Phase Three Phase
INPUT PARAMETERS
Voltage 110VAC / 115VAC / 120VAC
220VAC / 230VAC / 240VAC
(Optional: Others)
190VAC / 200VAC / 210VAC
380VAC / 400VAC / 415VAC
440VAC / 460VAC / 600VAC
(Optional: Others)
Voltage Range ±10% / ±15% / ±20% ±10% / ±15% / ±20%
Connection 2W (P+N) 3W (3P) / 4W (3P+N)
Frequency 50Hz, 60Hz or 400Hz (±15%)
Rectifier Type Full Bridge 6-Pulse / 12-Pulse
Power Factor >0.7 0.8 (6-Pulse) / 0.9 (12-Pulse)
THDi <50% <30% (6-Pulse) / <12% (12-Pulse)
OUTPUT PARAMETERS
Output Voltage 12VDC / 24VDC / 48VDC / 60VDC / 110VDC / 125VDC / 220VDC / 250VDC / 400VDC / 600VDC (Optional: Others)
Output Current 10A – 200A 10A – 5000A
Efficiency 75% – 87% 80% – 94%
Voltage Regulation <0.5%
Current Regulation <2%
Overload Current limiting at 100% of nominal current (adjustable)
Ripple <4% <1%
BATTERY PARAMETERS
Battery Type VRLA / OPzV / OPzS / Ni-Cd
Charge Voltage VRLA / OPzV / OPzS: 2.23VDC – 2.35VDC (Float), 2.40VDC (Boost/Equalize)
Ni-Cd: 1.42VDC (Float), 1.47VDC – 1.7VDC (Boost/Equalize)
Charge Current VRLA / OPzV / OPzS: 10-15% of battery capacity
Ni-Cd: 20% of battery capacity
Boost Duration 0 – 20 hours (adjustable)
Voltage Adjustment Range 80% – 125% nominal voltage
PHYSICAL CHARACTERISTICS
Cabinet Type Upright (Optional: others)
Cabinet Color RAL7032, RAL7035 (Optional: others)
Protection Class IP20 (Optional: IP21 – IP55)
Cooling Fan-cooled (Optional: natural, water cooling, smart fan)
Cable Entry Bottom (Optional: top, rear, side)
ENVIRONMENTAL CONDITIONS
Storage Temperature -25°C / +70°C
Operating Temperature -10°C / +50°C
Humidity 0% – 95% (Non-condensing)
Altitude 1000m (1% derating for every 100m above 1000m)
Noise 55dB – 75dB
Isolation 1500VAC / 2000VAC / 3000VAC
Insulation Resistance 200MΩ
COMMUNICATION
Standard Communication ModBus RTU (RS232) (Optional: RS485, TCP/IP, SNMP, IEC61850)
Parallel Operation Passive: Unlimited (Optional: active up to 4 units)
HMI LED/LCD Panel (Optional: touchscreen)
Languages Turkish, English, German, Dutch, Portuguese, Spanish, Russian
PROTECTIONS
Battery Protection Temperature compensation, LVD, current limiting
Input / Output Protection MCB or MCCB
AC line fault, DC low/high alarm
Overcurrent, ground fault, overtemperature
ADDITIONAL FEATURES (OPT.)
Load Output Diode or DC/DC converter
Measurements Input/Output voltage and current, battery data
DC Power Battery monitoring when AC is disconnected
Protection Fan failure, fuse, parallel fault, high ripple
STANDARDS
EN62310-1 General safety requirements
EN62310-2 EMC requirements
EN62310-3 Performance and test requirements

No documents found for this product.