Conceptpower DPA500
Conceptpower DPA500
ABB's modular uninterruptible power supply (UPS) Conceptpower DPA 500, designed for medium and large-scale data centers, meets power requirements from 100 kW to 3 MW and provides maximum availability for those seeking zero downtime and a low total cost of ownership.
Conceptpower DPA 500 offers 100 to 500 kW (vertical scalability) of power protection in a single cabinet (between one and five modules). Cabinets can operate in a parallel configuration to create a system up to 3 MW (horizontal scalability).
Conceptpower DPA 500 offers 100 to 500 kW (vertical scalability) of power protection in a single cabinet (between one and five modules). Cabinets can operate in a parallel configuration to create a system up to 3 MW (horizontal scalability).
- Features
- Parameters
- Documents
- Get a Quote
- Scalable modular UPS system from 100 kW to 3 MW
- Online double conversion technology
- Transformer-free design
- Easy capacity expansion with true modular architecture
- Horizontal and vertical scalability up to 3 MW
- Independent operation in each module (Decentralized Parallel Architecture)
- Structure that eliminates the risk of a single point of failure
- Online module replacement (hot-swap / online swap) support
- Ability to add and remove modules during operation (uninterrupted maintenance)
- Ideal solution for zero downtime requirements
- 1.0 output power factor (kVA = kW)
- Up to 96% AC-AC efficiency
- ≥ 99% efficiency in Eco mode
- Low total cost of ownership (TCO)
- Easy maintenance with front access
- Top and bottom cable entry support
- Internal back-feed protection
- Separate display on each module + touchscreen for the entire system
- Flexible structure with “pay as you grow” investment
- High availability (99.9999%) for data centers and critical loads
| GENERAL DATA | |
|---|---|
| System Power Range | 100kW – 3MW |
| Nominal Power / Module | 100kW |
| Nominal Power / Cabinet | 500kW |
| Output Power Factor | 1.0 |
| Topology | Double conversion, transformerless, modular, Decentralized Parallel Architecture |
| Parallel Configuration | Up to 5 modules in a single cabinet (500kW) / up to 6 cabinets in parallel (3MW) |
| Cable Entry | Top or bottom (standard) |
| Serviceability | Full front serviceable |
| Backfeed Protection | Internal (standard) |
| INPUT | |
| Nominal Input Voltage | 3×380/220 V + N, 3×400/230 V + N, 3×415/240 V + N |
| Voltage Tolerance |
Load < 100%: (-10%, +15%) Load < 80%: (-20%, +15%) Load < 60%: (-30%, +15%) |
| Input Harmonic Distortion (THDi) | <3.5% (at 100% load) |
| Frequency Range | 35–70Hz |
| Power Factor | 0.99 (at 100% load) |
| Soft Start (Walk-in / Soft Start) | Yes |
| OUTPUT | |
| Nominal Output Voltage | 3×380/220 V + N, 3×400/230 V + N, 3×415/240 V + N |
| Voltage Tolerance | <±1% (static load) / <±4% (dynamic load) |
| Voltage Distortion | <2% (linear load) / <4% (non-linear load) |
| Frequency | 50 or 60Hz (selectable) |
| EFFICIENCY | |
| AC-AC | Up to 96% |
| Eco Mode | ≥ 99% |
| ENVIRONMENT | |
| Protection Class | IP20 |
| Storage Temperature | -25° ~ +70°C |
| Operating Temperature | 0° ~ +40°C |
| Altitude | 1000m (without derating) |
| BATTERY | |
| Number of 12V Blocks | 40–50 blocks (flexible) |
| Battery Types | VRLA, flooded lead-acid, NiCd |
| Battery Charging | Independent charging per module |
| COMMUNICATION | |
| User Interface |
Graphical touchscreen (standard in each cabinet) LCD + mimic diagram on each module |
| Communication Ports | USB, RS-232, dry contact, SNMP (optional) |
| Customer Interface | Remote shutdown, generator interface, external bypass contact |
| STANDARDS | |
| Safety | IEC / EN 62040-1 |
| EMC | IEC / EN 62040-2 |
| Performance | IEC / EN 62040-3 |
| Manufacturing | ISO 9001:2015, ISO 14001:2015, OHSAS18001 |
| WEIGHT & DIMENSIONS | |
| Weight | Approx. 975 kg (500kW system, without batteries) |
| Dimensions (WxHxD) | 1580 x 1975 x 945 mm |