PLRM Series
PLRM Series
The PLRM Series is an advanced power protection solution designed for critical data centers and industrial facilities, featuring a modular structure that offers high power density and flexibility. With its 3:3 phase configuration, this system provides high availability, ensuring continuous operation even in the event of a fault, thanks to its modular design. Smart module management technology can put some power modules into sleep mode to maximize efficiency even at low load levels. Its 7-inch color touchscreen LCD and user-friendly interface make real-time monitoring and management of the system status extremely easy.
- Features
- Parameters
- Documents
- Get a Quote
- Offers easy scalability and maintenance thanks to its modular design.
- Features a 7-inch color touchscreen LCD with graphic display.
- Provides more active power with a unity output power factor (PF=1).
- Ensures energy savings with up to 95% efficiency in normal mode and 98% in ECO mode.
- Offers grid-friendly operation with low input current harmonic distortion (THDi < 3%).
- Maintains high system efficiency even at low loads thanks to smart module management.
- Minimizes battery usage in challenging grid conditions with a wide input voltage range (304-478Vac).
- Offers flexible backup times with internal and external battery support.
- Provides comprehensive communication options with RS232, RS485, dry contacts, and optional SNMP.
- Features full protection and alarm systems for conditions such as short circuit, overload, over-temperature, and low battery.
- Achieves over 90% energy savings while being tested at full load with energy internal circle technology.
| MAIN FEATURES | |
|---|---|
| Phase | 3 Phase + Neutral + Ground, 380V / 400V / 415V |
| Type | Modular |
| Capacity | 20kVA, 40kVA, 60kVA, 80kVA, 90kVA, 120kVA, 160kVA, 200kVA, 240kVA, 300kVA, 400kVA, 500kVA |
| PARAMETERS | |
| Input Voltage | 380 / 400 / 415 VAC |
| Input Voltage Range | 304–478 VAC (phase-to-phase), at full load 228–304 VAC (phase-to-phase), load linearly decreases depending on minimum phase voltage |
| Input Power Factor | ≥0.99 |
| Input Frequency | 40Hz – 70Hz |
| THD | THDi <3% @ 100% linear load |
| Output Voltage | 380 / 400 / 415 VAC |
| Voltage Regulation | ±1.5% |
| Output Power Factor | 1 |
| Efficiency | Normal mode: 95% ECO mode: 98% Battery mode: 94.5% |
| Crest Factor | 3:1 |
| THD | <1% (linear load), <5.5% (non-linear load) |
| Overload | 110%: 1 hour 125%: 10 min 150%: 1 min >>150%: 200 ms |
| Battery | Internal and external battery support depending on power |
| Display | LCD + LED, Touchscreen + Keyboard |
| IP Class | IP20 |
| Protection | Short circuit, overload, over-temperature, low battery, fan failure alarm |
| Communication | Standard: RS232, RS485, dry contacts Optional: SNMP |
| ENVIRONMENT | |
| Noise (1 meter) | 72dB @ 100% load; 69dB @ 45% load |
| Operating Temperature | 0 – 40°C |
| Storage Temperature | -25°C – 70°C |
| Humidity | 0% – 95% (non-condensing) |
| Altitude | < 1500 m |
| STANDARDS | |
| EN62040-1 | General and Safety Requirements for UPS |
| EN62040-2 | Electromagnetic Compatibility (EMC) Requirements for UPS |
No documents found for this product.