PowerValue 11-31T 10-20kVA

The ABB PowerValue 11/31 T is an uninterruptible power supply system designed to protect critical single-phase applications up to 20 kVA, featuring a transformerless, true online double conversion (VFI), compact tower type. With its true online double conversion system, the PowerValue 11/31 T protects your loads with high efficiency even against severe disturbances that may exist in the electrical grid. The PowerValue 11/31 T possesses all the necessary features to offer reliable power, low operating costs, long battery life, easy maintenance, and complete flexibility for its users.
  • Features
  • Parameters
  • Documents
  • Get a Quote
  • Energy savings thanks to 93% efficiency
  • 97% efficiency in ECO mode
  • Low harmonic distortion (<5% THDi) and active power factor correction (0.99 input power factor) eliminate interference from other equipment on the grid
  • Parallel and redundancy capability (up to 4 units in parallel) increases system capacity and availability
  • Integrated automatic and manual bypass simplifies maintenance and reduces the need for external panels.
  • Frequency converter operation for conversion between 50 – 60 Hz
  • Compact solution providing 5-16 min runtime with internal batteries
  • The same model supports different connection arrangements: three-phase and single-phase inputs, as well as single and dual input feeds
General Data 10 kVA 10 kVA S 10 kVA B 10 kVA B2 20 kVA 20 kVA S 20 kVA B
Max. Output Power 9 kW 18 kW
Output Power Factor 0.9
Topology Online double conversion
Parallel Configuration Up to 4 units
Internal Battery No Yes Yes No No No Yes
INPUT
Nominal Input Voltage 1 phase + N: 220 / 230 / 240 VAC
3 phase + N: 380 / 400 / 415 VAC
Input Voltage Range 1 phase + N: 110–276 VAC
3 phase + N: 190–486 VAC
Input Current Harmonic Distortion (THDi) <5% (linear load), <7% (non-linear load)
Frequency Range 45–55 Hz for 50 Hz systems / 55–65 Hz for 60 Hz systems
Power Factor ≥0.99
OUTPUT
Nominal Output Voltage 220 / 230 / 240 VAC
Voltage Tolerance ±2%
Voltage Distortion <2% (linear load), <5% (non-linear load)
Overload Capacity 1 min: 110–130% / 5 min: 105–110%
100 ms: >150% / 10 sec: 130–150%
Nominal Frequency 50 Hz or 60 Hz
Crest Factor 3:1 (load supported)
EFFICIENCY
Overall Efficiency Up to 93.1% Up to 93.9%
Eco Mode ≥97%
ENVIRONMENT
Protection Class IP20
Storage Temperature -15°C ~ +60°C (UPS), 0°C ~ +35°C (battery)
Operating Temperature 0°C ~ +40°C
Relative Humidity 0 – 95% (non-condensing)
Altitude 1000 m (without derating)
BATTERY
Battery Type VRLA (sealed lead-acid)
Internal Battery 1 × 24 2 × 24 2 × 24
Battery Capacity 9 Ah 9 Ah 9 Ah
Charging Current 4 A 8 A 4 A 4 A 4 A 8 A 4 A
Charging Time 3 hours (to 90%) 8 hours (to 90%) 8 hours (to 90%)
COMMUNICATION
User Interface LCD
Communication Cards (optional) Network interface (SNMP card), dry contact card (AS400)
STANDARDS
Safety IEC / EN 62040-1
EMC IEC / EN 62040-2
Performance IEC / EN 62040-3
Manufacturing ISO 9001:2015, ISO 14001:2015, OHSAS18001
WEIGHT & DIMENSIONS
Weight 56 kg 65 kg 116 kg 178 kg 67 kg 68 kg 190 kg
Dimensions (WxHxD mm) 350×890×715 350×890×715 350×890×715 350×890×715 350×890×715 350×890×715 350×890×715